Installation Note IN0049


Appendix VI: Fronius SCERT “Backup Ready” Connection

The following steps are for when Selectronic Certified SCERT Fronius units are installed without an SP PRO.

  • A link must be fitted to the orange Fronius Datamanager Connector from the + pin to IO 2 pin so that Fronius SCERTs can produce full power.

  • The country code must be set to AU  Australia.


NOTE: The link is only required when the SCERT inverter is installed without an SP PRO.